Appendix
204
W 01 705 Operating hours alarm pump 5 ctrl 1 Reset operating hours
W 02 705 Operating hours alarm pump 5 ctrl 2 Reset operating hours
W 01 706 Operating hours alarm pump 6 ctrl 1 Reset operating hours
W 02 706 Operating hours alarm pump 6 ctrl 2 Reset operating hours
W 01 711 Failure of pump 1 ctrl 1 check pump
1)
W 02 711 Failure of pump 1 ctrl 2 check pump
1
W 01 712 Failure of pump 2 ctrl 1 check pump
1
W 02 712 Failure of pump 2 ctrl 2 check pump
1
W 01 713 Failure of pump 3 ctrl 1 check pump
1
W 02 713 Failure of pump 3 ctrl 2 check pump
1
W 01 714 Failure of pump 4 ctrl 1 check pump
1
W 02 714 Failure of pump 4 ctrl 2 check pump
1
W 01 715 Failure of pump 5 ctrl 1 check pump
1
W 02 715 Failure of pump 5 ctrl 2 check pump
1
W 01 716 Failure of pump 6 ctrl 1 check pump
1
W 02 716 Failure of pump 6 ctrl 2 check pump
1
W00 801 simulation level swichted on switch off level simulation
(s. "level" menu)
W01 802
W02 802
simulation sensor 01 or 02 switched on switch off simulation
W01 803
W02 803
W01 804
W02 804
simulation flow switched on switch off simulation
(see "flow" menu)
W01 805 simulation current 01 switched on switch off simulation
(s. "output/calculations" menu)
W02 806 simulation current 02 switched on switch off simulation
(see "output/calculations" menu)
W01 807
...
W06 807
simulation relay 01 - 06 switched on switch off simulation
W01 808
W02 808
sensor 01 or 02 switched off switch on sensor
(see "device properties/sensor management" menu)
W01 809
W02 809
current calibration D/A active
A00820
...
A00832
Different units for calculation of average
value, sum, difference or rake control
Check the units of the respective basic calibrations
(s. "level" or "flow" menu)
1) After a repair of the pump the pump control must be reset (chapter 5.3.2) or the FMU90 must be switched off and
on.
Code Description of error Remedy