2-16
Step 4: Configuring the Fiber Test
4-1 Turn the rotary switch to SETUP.
4-2 Use
, to highlight Fiber; then press 0.
4-3 Use
, to highlight Remote End Setup; then
press
0.
4-4 Use
,) to highlight Smart Remote; then
press
0.
4-5 Use
, and 0 to enter the settings listed
below. Use
+ to find settings on other tabs.
Bi-Directional: No
Number of Adapters: Enter the number of
adapters used in the cabling you will test. For
example, if the cabling has one connector at
each end, enter 2.
Number of Splices: Enter the number of splices
in the cabling you will test.
Connector Type: Select the type of connector
used in the cabling you will test.
Test Method: Method B
Step 5: Setting the Reference
5-1 Clean the connectors on the tester and the four
patch cords.
5-2 Turn the rotary switch to SPECIAL FUNCTIONS. Press
0 to select Set Reference. If both a fiber module
and twisted pair adapter are attached, select Fiber
Module next.
5-3 Connect the tester and smart remote as shown in
Figure 2-10; then press
2.