Certifying Twisted Pair Cabling
Twisted Pair Autotest Results 3
3-23
1
2
3
4
5
6
7
8
amd11f.eps
A The location of the ACR results. Press J to switch
between the tester and smart remote.
B The overall ACR result. “PASS*/FAIL* Results” on page 3-12
describes results marked with an asterisk.
C Magnification level for the plot. Use AD to zoom
in or out at the cursor’s location.
D Measured ACR for the cable pairs. Higher ACR means better
cabling performance.
E The limit line (in red) for ACR. The higher the
measurements rise above the limit line, the better the
cabling performance. Press
L to see plots of individual
pairs.
F The cursor and its location on the frequency scale. When
you first view the plot, the cursor is placed at the worst
margin. Use
BC to move the cursor.
G The measured ACR and margin at the cursor’s position.
Margin is the difference between the measured value and
the limit. Margin is negative if the pair failed.
H The horizontal scale is the frequency range in megahertz.
The vertical scale is the ACR range in decibels.
Figure 3-17. ACR Plot