7. Touch “Yes” on the verification screen.
No Yes
Function Settung
Function setting will be performed. OK?
ERROR
GOOD
[002–01]
[30]
[01]
Address
Function No.
Setting No.
Function Setting
Back Setting
[002–01]
[30]
[ – ]
Address
Function No.
Setting No.
Function Setting
Back Setting
• When the setting is properly set up on the indoor unit, the set number will be displayed in
Setting No. (GOOD)
• When the setting is not set up correctly, “-” is displayed in Setting No. (ERROR) Back to the
previous step and perform the setting again.
RELATED LINKS
"Completion of setting mode" on page 07-48
"Function details" on page 07-108
¢ Setting up each indoor unit
Setting must be performed on each indoor unit by repeating following procedures.
• "Preparation" on page 07-102
• "Indoor unit function setting" on page 07-102
Wired remote
controller
(Touch panel)
Wired remote
controller
(Touch panel)
Wired remote
controller
(Touch panel)
0001 0101 0201 1301 1401 15010 0 0 0 0 0
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
¢
Resetting the power after setting up all indoor units
NOTES:
• If the reset is not performed, function cannot be read correctly.
• After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
– After the 2 minutes has passed, power can be restored.
– The set function is stored in the PCB and will remain in memory even when the power of in-
door unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
• Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
2-8. Indoor unit (setting by UTY-RNR
Z)
- (07-104) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION