Access control applications
3.20 EST3 Installation and Service Manual
For the door contact input loop:
Device Type = Security P Monitor
Input Circuit Partition = as determined by project
Max Delta Count = as determined by project
Delays = None
Application = Emergency Exit Door Contact
• Personality = Basic
For the request to exit switch:
Device Type = Monitor
Input Circuit Partition = None
Max Delta Count = not applicable
Delays = None
Application = Request to Exit with Delayed Egress
Personality = N.O. with Trouble
ACDB operation
When an employee badges in or out at the door, the CRC
bypasses the door contact for a specified period of time. This is
called the Bypass Time, and is specified in the ACDB.
The duration of the CRCSND horn is also specified in the
ACDB, as the Emergency Exit Sounder Time. This can be set to
any value between 0 and 255 seconds.
Setting the value to 0 seconds effectively inhibits the CRCSND.
Setting the value to 255 seconds programs the CRC to operate
the CRCSND until the CRC is manually reset by badging at the
CRC card reader.