EST3 Installation and Service Manual vii
UL 864 9th edition requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Programmable feature or
option
Permitted
in UL 864?
(Y/N)
Possible settings Settings permitted in
UL 864
Enable Supervision
(telephone line is supervised
for ground faults, a single
open line, or a wire-to-wire
fault)
Y No
Yes
Yes
DACT Settings - Line 2
Installed (single line or dual
line dialer)
Y No
Yes
Yes
Trouble Resound (panel
resound)
Y Disabled (0)
1 second to ~99 hours
Disabled [2]
0 to 24 hours
AC Power Delay Y Disabled
1 minute to 45 hours
1 to 3 hours
Event message routing Y All Cabinets
No Cabinets
User defined routes (1
to 15)
All Cabinets
No Cabinets [3]
User defined routes (1 to
15) [4]
Event message display
filtering: Alarm, Supervisory,
and Trouble options
Y Enabled
Disabled
Enabled
Disabled [5]
Delays (programmed in rules) Y 0 to 240 seconds 0 to 240 seconds [6]
CMS event reporting priority
(programmed in rules)
Y 1 to 255 1 to 255 [7]
CMS activate and restore
messages (programmed in
rules)
Y Send on activation
Send on restoration
Activation and
restoration triggers must
match the message type
4-state alarm IDC N N/A In Signature module
configuation, personality
code 18 is prohibited
[11]