Listing requirements 
EST3 Installation and Service Manual    C.5 
 —or— 
  KPDISP Keypad Display 
• FireWorks 
•  3-SAC Security Access Module 
•  Signature Controller Modules 
•  SIGA-MD Motion Detector 
•  SIGA-SEC2 Security Loop Module 
Additional requirements: 
•  System must be connected to a FireWorks workstation 
•  Standby power must provide 24 hours of standby with 15 
minutes of alarm 
•  Maximum entry or exit delay must be 60 seconds 
•  System must be programmed to transmit opening and 
closing messages to the central monitoring station 
•  System must be programmed to provide closing 
confirmation (ring-back) at the arming station 
Central station with local bell timeout using a 3-
MODCOM 
Standard: UL 1610 
Minimum hardware: 
•  3-RCC7 Remote Closet Cabinet 
•  ATCK Attack Kit 
•  3-TAMPRCC Cabinet Tamper Switch 
•  Central Processor Unit (CPU) 
•  3-PPS/M Primary Power Supply 
•  Main LCD Display (LCD) 
 —or— 
  KPDISP Keypad Display 
•  3-MODCOM Modem Communication Module 
•  3-SAC Security Access Module 
•  Signature Controller Module 
•  Listed bell and bell housing: Ademco model AB12M Bell in 
Box 
•  24DC12 12 Vdc Voltage Regulator with Security Bell 
Interface 
•  3-IDC8/4 Traditional Zone I/O Module 
•  SIGA-MD Motion Detector 
•  SIGA-SEC2 Security Loop Module 
Additional requirements: 
•  Standby power must provide 24 hours of standby with 15 
minutes of alarm 
•  Maximum entry or exit delay must be 60 seconds