Service and troubleshooting 
EST3 Installation and Service Manual  8.41 
The panel performs a ground fault test for 2 seconds at 
40-second intervals. If the system is working properly, the 
voltage between earth ground and logic negative should be 
between 12.3 Vdc and 16.8 Vdc during the 2-second test. The 
system reports a ground fault when the voltages are less than 
12.3 and more than 16.8. In a non-faulted system, the voltage 
outside the 2-second test period may float randomly, but if the 
system is faulted the voltage is likely to be a fixed value such as 
3 or 19. 
Substituting known good Signature series 
devices 
When substituting a “known good” detector or module in place 
of a suspect device, one of two scenarios can take place. 
If the substituted device is the same model as the suspect device, 
the system accepts it with no further operator action. When the 
substituted device is installed, the system goes into trouble. 
When the quantity of devices defined on the circuit is reached, 
the system automatically remaps the circuit, stores the revised 
information, and returns to normal. This process may take a few 
minutes. 
If the substituted device is a different model than the suspect 
device, when the device count is correct, the Signature controller 
module automatically remaps the circuit. A trouble occurs at the 
address of the suspect device as the result of a map fault, because 
the known good device’s parameters differ from those of the 
suspect device that was removed from the circuit. You must 
accept the parameters of the known good device to remove the 
map fault. These can be changed later. 
You cannot use device substitution as a troubleshooting 
technique for Signature security devices. By design, the 
Signature controller does not automatically remap a replaced 
security device. This is intended to prevent swapping a security 
device with one that has been compromised for criminal 
purposes. 
Detectors 
When one or more devices are removed from a Signature Data 
Circuit for servicing, as shown in Figure 8-11, the panel will 
display a trouble condition for each device. If the System 
Definition Utility program (SDU) were connected to the panel, 
the DSDC Status screen would also indicate a trouble condition 
and the need to re-map. 
If the detector is removed from an isolator base, the isolator will 
transfer.