Service and troubleshooting   
8.42  EST3 Installation and Service Manual 
[3MAP1.CDR]
001
101
102
IPHS
S/N 33-1
IPHS
S/N 33-1
IPHS
S/N 34-1
PHS
S/N 34-1
Control Panel Display
DSDC Status Screen
Removed for service
CT2
S/N 49-1
P-codes 01/01 
CT1
S/N 48-1
P-code 02 
102
203
204
ROUBLE ppmm101
       ppmm102
COMMON TROUBLE
MAP PENDING
 
Figure 8-11: Detectors removed for service 
If these devices are returned to their original locations, as shown 
in Figure 8-12, the map supervision function recognizes the 
detectors have been returned as originally installed (and 
mapped), and takes no additional action. 
[3MAP2.CDR]
001
101
IPHS
S/N 33-1
PHS
S/N 34-1
Control Panel Display
DSDC Status Screen
The same detectors
returned to service in
their original
locations.
CT2
S/N 49-1
P-codes 01/01 
CT1
S/N 48-1
P-code 02 
102
203
204
 
Figure 8-12: Detectors returned to service in original locations 
If the devices are returned to the Signature Data Circuit but are 
not returned to their original locations, the map supervision 
function recognizes that previously mapped serial numbers 
occupy new map locations. Once the mapping supervision 
function has recognized the need to re-map the circuit, the panel 
is put in the “map pending” state. Once in the map pending state, 
the panel will automatically re-map the circuit when the quantity 
of devices re-installed on the circuit is equal to or greater than 
the quantity of devices defined in the original map. If the panel 
were connected to a computer running the SDU Program, the 
DSDC status function would indicate map pending.