Service and troubleshooting
8.42 EST3 Installation and Service Manual
[3MAP1.CDR]
001
101
102
IPHS
S/N 33-1
IPHS
S/N 33-1
IPHS
S/N 34-1
PHS
S/N 34-1
Control Panel Display
DSDC Status Screen
Removed for service
CT2
S/N 49-1
P-codes 01/01
CT1
S/N 48-1
P-code 02
102
203
204
T
ROUBLE ppmm101
ppmm102
COMMON TROUBLE
MAP PENDING
Figure 8-11: Detectors removed for service
If these devices are returned to their original locations, as shown
in Figure 8-12, the map supervision function recognizes the
detectors have been returned as originally installed (and
mapped), and takes no additional action.
[3MAP2.CDR]
001
101
IPHS
S/N 33-1
PHS
S/N 34-1
Control Panel Display
DSDC Status Screen
The same detectors
returned to service in
their original
locations.
CT2
S/N 49-1
P-codes 01/01
CT1
S/N 48-1
P-code 02
102
203
204
Figure 8-12: Detectors returned to service in original locations
If the devices are returned to the Signature Data Circuit but are
not returned to their original locations, the map supervision
function recognizes that previously mapped serial numbers
occupy new map locations. Once the mapping supervision
function has recognized the need to re-map the circuit, the panel
is put in the “map pending” state. Once in the map pending state,
the panel will automatically re-map the circuit when the quantity
of devices re-installed on the circuit is equal to or greater than
the quantity of devices defined in the original map. If the panel
were connected to a computer running the SDU Program, the
DSDC status function would indicate map pending.