System calculations   
B.20  EST3 Installation and Service Manual 
Cabinet battery 
Use the following method to calculate the minimum ampere-
hour capacity of a battery required in order to operate a panel in 
the absence of AC power. Battery calculations must be 
performed separately for each cabinet in the system. 
Determine the total amount of current in milliamps required by 
all of the components that derive power from the battery while 
the panel is in standby mode. Multiply the total amount of 
standby current by the number of hours that the panel is required 
to operate in standby mode while on battery power. 
Determine the total amount of current in milliamps required by 
all of the components that derive power from the battery while 
the panel is in alarm mode. Multiply the total amount of alarm 
current by the number of minutes that the panel is required to 
operate in alarm mode while on battery power. Divide the result 
by 60 to convert minutes to hours. 
Add the total amount of standby current and the total amount of 
alarm current then divide the result by 1000 to convert to 
ampere-hours. Multiply this number by 1.2 to add a 20% safety 
factor to the calculations. 
EST3 is UL Listed for battery operation durations as follows: 
•  Standby: 60 hours max. 
•  Alarm: 30 minutes max.