Listing requirements
C.8 EST3 Installation and Service Manual
Standard line security is for stand-alone or networked EST3
systems only
Access control
Standard: UL 294
Minimum hardware:
Central Processor Unit (CPU)
3-PPS/M Primary Power Supply
Main LCD Display (LCD)
3-SAC Security Access Module
CRC or CRCXM Card Reader Controller
Note: The CRC or CRCXM Card Reader Controller is fully
functional and does not require a supportive PC for access
decisions. Refer to the CRC and CRCXM - Card Reader
Controller Installation Sheet.
Holdup alarm
Standard: UL 636
Minimum hardware:
3-RCC7 Remote Closet Cabinet
ATCK Attack Kit
3-TAMPRCC Cabinet Tamper Switch
Central Processor Unit (CPU)
3-PPS/M Primary Power Supply
Main LCD Display (LCD)
3-MODCOM Modem Communication Module
—or—
FireWorks
3-IDC8/4 Traditional Zone I/O Module
—or—
Signature Controller Module
—plus—
SIGA-CT1, SIGA-CT2, or SIGA-UM module
Listed compatible holdup IDC devices
Additional requirements:
Standby power must provide 24 hours of standby with 15
minutes of alarm
Maximum entry or exit delay must be 60 seconds
Systems using a 3-MODCOM must be configured using two
phone lines with line-cut detection
—or—
a single line with 24-hour test
IDC8/4 devices must be configured as a security zone (in the
SDU, Hard Zone Type = SECURITY)