Listing requirements
EST3 Installation and Service Manual C.7
Proprietary using 3-MODCOM or FireWorks
Standard: UL 1076
Minimum hardware:
• 3-RCC7 Remote Closet Cabinet
• ATCK Attack Kit
• 3-TAMPRCC Cabinet Tamper Switch
• Central Processor Unit (CPU)
• 3-PPS/M Primary Power Supply
• Main LCD Display (LCD)
—or—
KPDISPKeypad Display
• 3-MODCOM Modem Communication Module
—or—
FireWorks
• 3-SAC Security Access Module
• Signature Controller Modules
• SIGA-MD Motion Detector
• SIGA-SEC2 Security Loop Module
Additional requirements:
• Standby power must provide 24 hours of standby with 15
minutes of alarm
• Maximum entry or exit delay must be 60 seconds
• Systems using a 3-MODCOM must be configured using two
phone lines with line-cut detection
—or—
a single line with 24-hour test
• System must be programmed to provide closing
confirmation (ring-back) at the arming station
Proprietary with standard line security
Standard: UL 1076
Minimum hardware:
• 3-CAB5, 3-CAB7, 3-CAB14, 3-CAB21, 3-RCC7, 3-RCC14,
or 3-RCC21 with 3-CHAS7
• 3-TAMP, 3-TAMP5, or 3-TAMPRCC Cabinet Tamper
Switch
• Central Processor Unit (CPU)
• 3-PPS/M Primary Power Supply
• 3-IDC8/4
—or—
3-SSDC(1) or 3-SDDC(1) with SIGA-CT1, SIGA-CT2, or
SIGA-UM
• 3-RS485A, 3-RS485B, or 3-RS485R
Additional requirements: