Power-up and testing 
EST3 Installation and Service Manual  6.19 
5.  After all detectors have been individually inspected, run a 
Sensitivity report, using the Reports command. 
Addressable analog detectors on a 3-AADC(1) 
Module circuit 
1.  Verify that all components are installed using accepted 
workmanship standards. 
2.  Individually activate each detector. Verify that the 
appropriate Alarm and location message is displayed on the 
LCD module. Verify that the detector initiates the 
appropriate system responses. 
3.  Duct mounted detectors should be tested to verify that 
minimum/maximum airflow requirements are met. 
4.  Remove the detector from its base. Verify that the 
appropriate Trouble and location message is displayed on the 
LCD module. 
5.  After all detectors have been individually inspected, run a 
Sensitivity report, using the Reports command. 
Traditional 2-wire smoke detectors connected to 
3-IDC8/4 modules 
1.  Verify that all components are installed using accepted 
workmanship standards. 
2.  Individually activate each detector. Verify that the 
appropriate Alarm and location message is displayed on the 
LCD module. Verify the detector circuit initiates the 
appropriate system responses. 
3.  Duct mounted detectors should be tested to verify that 
minimum/maximum airflow requirements are met. 
4.  Remove the detector from its base. Verify that the 
appropriate circuit Trouble and location message is 
displayed on the LCD module. 
Conventional 2-wire smoke detectors connected 
to SIGA-UM modules 
1.  Verify that all components are installed using accepted 
workmanship standards. 
2.  Verify that jumper JP1 on each SIGA-UM module is set to 
position 1/2. 
3.  Individually activate each detector. Verify that the 
appropriate Alarm and location message is displayed on the