Power-up and testing
EST3 Installation and Service Manual 6.19
5. After all detectors have been individually inspected, run a
Sensitivity report, using the Reports command.
Addressable analog detectors on a 3-AADC(1)
Module circuit
1. Verify that all components are installed using accepted
workmanship standards.
2. Individually activate each detector. Verify that the
appropriate Alarm and location message is displayed on the
LCD module. Verify that the detector initiates the
appropriate system responses.
3. Duct mounted detectors should be tested to verify that
minimum/maximum airflow requirements are met.
4. Remove the detector from its base. Verify that the
appropriate Trouble and location message is displayed on the
LCD module.
5. After all detectors have been individually inspected, run a
Sensitivity report, using the Reports command.
Traditional 2-wire smoke detectors connected to
3-IDC8/4 modules
1. Verify that all components are installed using accepted
workmanship standards.
2. Individually activate each detector. Verify that the
appropriate Alarm and location message is displayed on the
LCD module. Verify the detector circuit initiates the
appropriate system responses.
3. Duct mounted detectors should be tested to verify that
minimum/maximum airflow requirements are met.
4. Remove the detector from its base. Verify that the
appropriate circuit Trouble and location message is
displayed on the LCD module.
Conventional 2-wire smoke detectors connected
to SIGA-UM modules
1. Verify that all components are installed using accepted
workmanship standards.
2. Verify that jumper JP1 on each SIGA-UM module is set to
position 1/2.
3. Individually activate each detector. Verify that the
appropriate Alarm and location message is displayed on the