Centralized audio applications 
EST3 Installation and Service Manual  4.11 
Installation 
The URSM requires one-half of a standard mounting footprint 
and should be installed where the power pigtails can reach the 
power supply. 
The GFD and CT1 must be installed in the same enclosure, 
located adjacent to the fire alarm control panel. Jumper JP1 on 
the GFD should be set to the 2-3 position. 
Terminal connections 
Refer to Figure 4-6. 
Black pigtail = (-)24 Vdc power in 
Red pigtail = (+)24 Vdc power in 
TB1–1 to 3 = Channel 2, trouble relay contacts 
TB1–4 to 6 = Channel 1, trouble relay contacts 
TB1–7 = Channel 2, 70 Vrms audio riser input 
TB1–8 = Channel 2, 25 Vrms audio riser input 
TB1–9 = Firefighter’s Telephone riser input, Ch 2 
TB1–10 = Channel 2, Riser input, common 
TB1–11 = Channel 1, 70 Vrms audio riser input 
TB1–12 = Channel 1, 25 Vrms audio riser input 
TB1–13 = Firefighter’s Telephone riser input, Ch 1 
TB1–14 = Channel 1, Riser input, common 
Operation 
The trouble relay will activate 45–60 seconds after a circuit 
short, circuit open, or amplifier failure is detected.