Preventive maintenance   
7.2  EST3 Installation and Service Manual 
General 
Before commencing testing, notify all areas where the alarm 
sounds and off premises locations that receive alarm and trouble 
transmissions that testing is in progress. 
Records of all testing and maintenance shall be kept on the 
protected premises for a period of at least five (5) years. 
Required Tools: 
•  Slotted Screwdriver, Insulated 
• Digital multimeter 
• 1.1 kΩ 1 W resistor 
•  12 inch (30.5 cm) jumper lead with alligator clips 
•  Panel Door Key 
In addition, make sure you have the required system passwords. 
If the system includes access control applications, you'll need a 
construction card, or other valid access card. 
A complete check of installed field wiring and devices should be 
made at regular intervals, in accordance with NFPA 72 and ULC 
524 requirements. This includes testing all alarm and supervisory 
alarm initiating devices and circuits, and any off premise 
connections. 
Panel operation should be verified in the alarm, supervisory, and 
trouble modes. 
To ensure that the panel can be powered when primary power is 
lost, the batteries should be periodically inspected, tested, and 
replaced (as a minimum) every 4 years.