Service and troubleshooting 
EST3 Installation and Service Manual  8.35 
Signature data circuit (SDC) operation 
The advanced features of the Signature controller module 
perform a number of advanced operations. These operations are 
not always apparent from the panel controller. Table 8-26 lists a 
number of SDC conditions and describes the circuit’s operation. 
 
Table 8-26: SDC operation 
Condition Operation 
Remove a detector, then 
re-install the same detector in 
the same base. 
1.  The system displays a trouble with the detector’s label or 
address when the detector is removed. 
2.  The system restores completely when the detector is 
re-installed in its original base. 
Remove a module or pull 
station, then re-install the 
same device in the same 
location. 
1.  The system displays a trouble with the module’s label or 
address when the device is disconnected. 
2.  The panel restores completely when the device is re-installed 
in its original location. 
Remove a detector, then 
re-install a different detector of 
the same type in the same 
base. 
1.  The system displays a trouble with the detector’s label or 
address when the detector is removed 
2.  When the new detector is installed, the Signature controller 
module re-maps the circuit, replacing the S/N of the old 
detector with the S/N of the new detector. All the old 
detector’s sensitivity and verification settings are transferred 
to the new detector. The system will return to normal when 
mapping is finished. 
Remove a module or pull 
station, then re-install a 
different device of the same 
type in the same location. 
(SIGA-UM replacement 
modules must have jumper 
JP1 set in the same position 
as the original module.) 
1.  The system displays a trouble with the device’s label or 
address when the device is disconnected. 
2.  When the new device is installed, the Signature controller 
module re-maps the circuit, replacing the S/N of the old 
device with the S/N of the new device. If the devices are 
modules (not pull stations), the old module’s personality 
codes are transferred to the new module. The panel will return
to normal when mapping is finished. 
Remove a detector, then 
re-install a different type 
detector in the same base. 
1.  The system displays a trouble with the detector’s label or 
address when the detector is removed. 
2.  When the new detector is installed, the Signature controller 
module re-maps the circuit, replacing the S/N of the old 
detector with the S/N of the new detector. All the old 
detector’s sensitivity and verification settings (when 
applicable) are transferred to the new detector. The new 
detector will be operational, however the panel will be in 
trouble, indicating a device type mismatch. The System 
Definition Utility program must be used to re-assign the device
type to get the system out of trouble.