Listing requirements
C.4 EST3 Installation and Service Manual
Central Processor Unit (CPU)
3-PPS/M Primary Power Supply
Main LCD Display (LCD)
—or—
KPDISP Keypad Display
3-MODCOM Modem Communication Module
—or—
FireWorks
3-SAC Security Access Module
Signature Controller Modules
Listed bell and bell housing: Ademco model AB12M Bell in
Box
24DC12 12 Vdc Voltage Regulator with Security Bell
Interface
3-IDC8/4 Traditional Zone I/O Module
SIGA-MD Motion Detector
SIGA-SEC2 Security Loop Module
Additional requirements:
Standby power must provide 24 hours of standby with 15
minutes of alarm
Maximum entry or exit delay must be 60 seconds
System must be programmed for a minimum of 15 minutes
bell ring on alarm
System must be programmed to indicate bell timeout with an
LED
System power supply, bell power supply (24DC12), and bell
monitoring module (IDC8/4), must all be inside the ATCK
Attack Kit protected cabinet
Systems using a 3-MODCOM must be configured using two
phone lines with line-cut detection
—or—
a single line with 24-hour test
System must be programmed to provide closing
confirmation (ring-back) at the arming station
Central station connection using FireWorks
Standard: UL 1610
Minimum hardware:
3-RCC7 Remote Closet Cabinet
ATCK Attack Kit
3-TAMPRCC Cabinet Tamper Switch
Central Processor Unit (CPU)
3-PPS/M Primary Power Supply
Main LCD Display (LCD)