Service and troubleshooting   
8.70  EST3 Installation and Service Manual 
Addressable analog diagnostic tools 
The SDU addressable analog diagnostic tools are designed to 
assist in isolating and correcting faults with addressable analog 
circuits, detectors, and modules. 
System definition utility 
The quickest method for isolating most common problems is 
with the Systems Definition Utility (SDU) diagnostic tools. 
1.  Connect the computer that runs the SDU to the system, and 
open the appropriate project. 
If the actual project is not available, create a phantom project 
with an empty 3-AADC1 circuit and connect directly to the 
module in question. 
2.  From the menu bar, select Tools > System Sensor > 
Diagnostics. 
3.  On the Options tab, clear the selection from Message 
Counters, and upload. Trouble Tables, Ready 
Communication, and Display as Device Addresses should be 
selected. 
4.  Click: Upload AADC Tables. 
5.  Select the Status Tables tab when the table upload is 
complete. 
Addressable analog diagnostic table interpretation 
Each table lists the addresses for the modules and sensors 
reporting the associated condition with a total at the bottom. 
When displayed as Device Addresses, sensor addresses 
correspond with the rotary switch setting, and modules are 
reported as 100 plus the rotary switch setting. Multiple faults 
will make the process more difficult but the addresses noted in 
the fault tables make an excellent starting point 
 
Table 8-40: Addressable analog diagnostic table interpretation 
Table Name  Description  Possible causes 
Communicating 
Devices 
Lists sensor and module 
addresses talking to the 
3-AADC1. 
Total number of communicating devices 
should equal number of installed devices. 
If total is low, see Communication Fault 
table for missing or not connected 
device(s). 
If total is high, see Unexpected Fault table 
for extra device(s) installed on circuit. 
Internal Fault  Devices reporting an internal 
failure 
Replace device