EasyManua.ls Logo

GE Security EST3 - Multiple 3-MODCOM Modules

GE Security EST3
388 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Security applications
EST3 Installation and Service Manual 2.13
Multiple 3-MODCOM modules
You can install more than one 3-MODCOM Modem
Communicator module in a system. Two or more 3-MODCOM
modules can be installed in the same cabinet. Two or more
cabinets can contain 3-MODCOM modules.
There are several reasons for using multiple 3-MODCOMs:
Redundant communication to a CMS
Backup of critical communication links
Dedicated security transmission hardware
In a redundant communication system both 3-MODCOMs are
programmed to transmit the same message to different receivers
at the CMS or at different CMS installations.
One 3-MODCOM can be programmed to back up another. This
guarantees CMS communication (or TAP paging) should one
panel in the system become disabled.
In a multiple tenant application, there may be a high volume of
ACDB/KDC program traffic. You can design such systems with
a second 3-MODCOM, dedicating the first module to
ACDB/KDC traffic, and the second module to CMS
transmissions. This prevents contention for communication
channels.
Overall limits for the number of 3-MODCOM modules are:
10 modules per node
10 modules total per network

Table of Contents