viii EST3 Installation and Service Manual
Programmable feature or
option
Permitted
in UL 864?
(Y/N)
Possible settings Settings permitted in
UL 864
Alarm zone group members Y Alarm device type
Pull device type
Heat device type
Verified smoke device
type
Water flow device type
Alarm device type [8]
Pull device type
Heat device type
Verified smoke device
type
Water flow device type
AND group members Y Alarm device type
Pull device type
Heat device type
Verified smoke device
type
Water flow device type
Alarm zone device type
Fire zone device type
Matrix group device
type
Alarm device type [8]
Pull device type
Heat device type
Verified smoke device
type [9]
Water flow device type
Alarm zone device type
Fire zone device type
Matrix group device type
AND group device activation
count
Y 1 to 255 1 to 255 [10]
Matrix groups: Members Y Alarm device type
Pull device type
Fire device type
Call point device type
Heat device type
Verified smoke device
type
Water flow device type
Alarm device type [8]
Pull device type
Fire device type [8]
Call point device type
Heat device type
Verified smoke device
type [9]
Water flow device type
Matrix groups: Device
activation count
Y 3 to 10 3 to 10 [10]