EST3 Installation and Service Manual ix
Programmable feature or
option
Permitted
in UL 864?
(Y/N)
Possible settings Settings permitted in
UL 864
Notes
[1] Allowed only when the supervising station supervises the telephone line and annunciates
fault conditions within 200 seconds
[2] Allowed only on control panels that transmit trouble event signals off premises
[3] Allowed only with monitor device types and switches
[4] Allowed only if user route includes the control panel
[5] Allowed only on nonrequired remote annunciators
[6] Allowed only when setting does not prevent the activation or transmission of alarm or
supervisory signals within 10 seconds or trouble signals within 200 seconds
[7] When priorities are used, alarm events must have a higher priority than supervisory and
trouble events.
[8] Allowed in alarm zone groups, AND groups, and matrix groups that are used to initiate the
release of extinguishing agents or water except when the addressable smoke detector's
alarm verification is used.
[9] Allowed only in alarm zone groups, AND groups, and matrix groups that are not used to
initiate the release of extinguishing agents or water
[10] A minimum device activation count of 2 is required if the AND group or matrix group is used
to initiate the release of extinguishing agents or water
[11] Personality code 18 is typically used when a short condition must be distinguished from an
alarm condition. This type of IDC is prohibited by UL 864.