Installation
EST3 Installation and Service Manual 5.17
If a CDR-3 Zone Coder is installed and connected to the AUX
input on a 3-ASU, include the following features in the initial
startup version of the project database:
Program a control/display module toggle switch that is to
turn on the amplifiers and select the Auxiliary channel.
Label the switch AUX_INPUT_ADJUST and add the
following rule to the rules file:
[3-ASU_AUX_INPUT_SETUP]
SW 'AUX_INPUT_ADJ':
AMPON '*' TO 'Ch_Aux*';