Installation   
  EST3 Installation and Service Manual 
5.38
When the 3-MODCOM is configured as a two-line dialer 
module, two incoming lines must be used and connections must 
be made to each line. 
Installing the 3-MODCOM module 
Make sure that panel power is off, then proceed as follows, 
1.  Use an antistatic wrist strap to ground yourself to an 
unpainted part of the cabinet. 
2.  Carefully remove the 3-MODCOM from the antistatic bag in 
which the module is packed. Always handle it by the edges 
or by the plastic door. 
3.  Place the bag on a flat work surface, then place the module, 
connector side up, on the empty bag. 
  Check for shipping damage. Orient the module so the two 
eight-position modular telephone jacks are on the top. 
4.  If a control / display module is needed, remove the blank 
front plate and attach the ribbon cable to the front of the 
3-MODCOM board. 
5.  Refer to the SDU cabinet report to determine the proper 
location for the module, then plug the module into the rail. 
  Be careful to align the module and rail sockets so that the 
pins are in the proper holes and that seat the module firmly. 
6.  Fasten the module in place with the push-pins. 
7.  Restore power to the panel. 
8.  Install wiring to module as described on the 3-MODCOM 
installation sheet. 
Connecting the 3-MODCOM to a telephone line 
Plug one end of the supplied telephone connecting cord (P/N 
3601370) into the telephone company line jack on the 
3-MODCOM. 
Do not plug the other end into the RJ-31X jack until you are 
ready to test the system. This prevents unnecessary interference 
with other equipment connect to the line downstream. 
When you are ready for final connections and testing, use the 
telephone company line jacks as follows: 
Line 1 jack  Line 2 jack 
Single-line dialer  Second line of 2-line dialer 
Incoming modem line 
For the installation of a fire alarm system in compliance with 
NFPA 72, the 3-MODCOM must be connected to loop-start