Power-up and testing
EST3 Installation and Service Manual 6.9
changes, the event sequence indicates a “3,” the active
Alarm events counter at the bottom of the display indicates
A003, the event type indicates fire alarm, and the local panel
buzzer resounds, and the first alarm message remains at the
top of the LCD window. Press the Alarm queue switch and
verify that the Alarm LED lights steady.
8. Use the previous and next message switches to verify that
you can scroll through all three messages in the alarm queue,
as indicated by the event sequence window.
9. Press the Reset switch. Verify that all initiating devices reset
and that all panel indicators clear except the power LED.
10. Initiate an active Monitor condition and verify that: the
Monitor LED flashes, the correct active Monitor device
message appears in the top and bottom windows of the LCD,
the active point counter changes, the event sequence
indicates a “1,” the active Monitor events counter at the
bottom of the display indicates M001, and the event type
indicates Monitor. Press the Monitor queue switch and verify
that the Monitor LED lights steady. Initiate a second active
Monitor condition and verify that the first Monitor message
remains at the top of the LCD window, that the second
Monitor event message appears at the bottom of the display,
the active point counter changes, the event sequence
indicates a “2,” the active Monitor events counter at the
bottom of the display indicates M002.
11. Initiate an active Trouble condition and verify that: the
Trouble LED flashes, the correct active Trouble device
message appears in the top and bottom windows of the LCD,
the local panel buzzer sounds, the Trouble relay transfers,
the active point counter changes, the event sequence
indicates a “1,” the active Trouble events counter at the
bottom of the display indicates T001, and the event type
indicates Trouble. Press the Trouble queue switch and verify
that the Trouble LED lights steady. Press the Panel Silence
switch to verify the panel buzzer silences and the Panel
Silenced LED lights. Initiate a second active Trouble
condition and verify that the first Trouble message remains
at the top of the LCD window, that the second Trouble event
message appears at the bottom of the display, the active
point counter changes, the event sequence indicates a “2,”
the active Trouble events counter at the bottom of the
display indicates T002.
12. Initiate an active Supervisory condition and verify that the
Supervisory LED flashes, the correct active Supervisory
device message appears in the top and bottom windows of
the LCD, the local panel buzzer sounds, the Supervisory
relay transfers, the active point counter changes, the event