Service and troubleshooting
8.54 EST3 Installation and Service Manual
Table 8-35: Mapping error messages
Message Suggested corrective action
The map tables are inconsistent. 1. Upload the current map.
2. Compare current map with expected map.
3. Write the map back to the Signature
controller module.
The actual SDC map does not match the stored
expected map.
1. Upload the current map.
2. Compare current map with expected map.
3. Write the map back to the Signature
controller module
Setting the Address in the device failed. 1. Review the Serial Number or Short
Address. If missing, replace the device.
2. Persistent problem is indicative of a wiring
fault.
Map supervision failure. The map in use has
invalid data. This error initiates an automatic
reconstruction of the map.
1. Please wait for automatic map
reconstruction to complete before
continuing.
Mapping supervision detected a change on the
SDC. A rebuild of the map was scheduled.
1. Please wait for automatic map
reconstruction to complete before
continuing.
Mapping supervision detected that the device
address or the short address of the device
being supervised has changed. A rebuild of the
map was scheduled.
1. Please wait for automatic map
reconstruction to complete before
continuing.
The mapping command failed, the sensor did
not draw current or it was not possible to obtain
stable mapping data from the SDC. A rebuild of
the map was scheduled.
1. Please wait for the automatic map
reconstruction to complete before
continuing.
Mapping was aborted by an external event,
such a new start on a device. A rebuild of the
map was scheduled.
1. Please wait for the automatic map
reconstruction to complete before
continuing.
Mapping supervision detected that the Device
Type of the Device being supervised has
changed. A Map Fault was flagged.
1. Replace the device.
2. Correct the Signature controller module
programming.
Mapping was aborted because there is short or
open on the SDC wiring.
1. An open or short on a Class A circuit.
2. A short across the entire Class B circuit.
3. A Reset may be needed to restart mapping.
Unable to recreate current map at panel
startup. The panel will re-map to reconstruct the
map.
1. Please wait for the automatic map
reconstruction to complete before
continuing.