Service and troubleshooting 
EST3 Installation and Service Manual  8.73 
differs for different objects and circumstances. Pull stations are 
polled much more frequently than detectors or modules. Devices 
that report communication failure are polled more often than 
devices that are not experiencing the failure. 
•  Devices with high message counts but few errors may be 
pull stations or devices that change state regularly such as 
monitor modules. 
•  Devices that have increased error counts and only marginally 
increased message counts may indicate wiring or device 
problems. 
•  Devices with low message counts and an equal number of 
errors are non-existent devices. 
•  All 198 addressed are polled occasionally to identify any 
devices that may have been installed and not configured. 
If the message and error counts are confused because of the 
length of time the circuit has been running, restarting the panel 
will cause a restart of the circuit and the zero the counters. You 
may need to monitor the circuit for twenty minutes or more 
before a trend in messages becomes apparent. Locating 
intermittent faults may require extended operating periods.