Service and troubleshooting   
8.78  EST3 Installation and Service Manual 
Addressable Analog circuit capacitance problems are typically 
caused by long wire runs, ground faults on the Addressable 
Analog circuit, improper T-taps, or improper shielding. 
If shielded wire is used, the shield must be treated as a third 
conductor. It must be free of all ground faults and have 
continuity throughout.
 If the wire capacitance is too large for the 
run length, the only remedies are to replace the wire with a cable 
having a lower capacitance per foot or install additional 
Addressable Analog modules, dividing the circuit into acceptable 
lengths. 
Ground faults 
Eliminating ground faults on the Addressable Analog circuit 
reduces the amount of capacitance on the Addressable Analog 
wiring. 
Verify the Addressable Analog circuit is free of ground faults. 
Correcting addressable analog circuit wiring 
problems 
If the Addressable Analog circuit is wired with improper T-taps 
or excessive capacitance, corrective measures include: 
•  Designing the Addressable Analog circuit properly and 
re-pulling the wire 
•  Balancing the circuit. Balancing the circuit can help in some 
cases but is not a substitute for proper wiring practice. If 
circuit balancing is required, call Technical Services for 
additional information.