System calculations
B.22 EST3 Installation and Service Manual
Form A: 3-SAC alarm and standby load
Device Qty Alarm
current
(mA)
Total alarm
current
(mA)
Standby
current
(mA)
Total
standby
current
(mA)
Standby
time
(Hours)
Amp
hours
(mAH)
KPDISP 100 35
CRC 950 940
CR-5355 72 70
CR-5365 31 25
CR-5395 24 20
CR-6005 20 20
Reader sounder 8 0
CRCSND 8 0
Strike rating
100 mA @ 12 V 33 0
150 mA @ 12 V 40 0
200 mA @ 12 V 42 0
250 mA @ 12 V 47 0
300 mA @ 12 V 51 0
35 mA @ 12 V 55 0
400 mA @ 12 V 58 0
450 mA @ 12 V 63 0
500 mA @ 12 V 65 0
Maglock rating
100 mA @ 12 V 80 80
150 mA @ 12 V 126 126
200 mA @ 12 V 156 156
250 mA @ 12 V 187 187
300 mA @ 12 V 233 233
350 mA @ 12 V 283 283
400 mA @ 12 V 376 376
450 mA @ 12 V 436 436
500 mA @ 12 V 470 470
Total alarm load (must be < 3.5 A) Total amp hours (Battery)
Note: Standby time = length of time that the device will draw standby current from battery. There
is no minimum standby time for access control.