Page #123 background image
Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 111
Option Description
Secondary receiver number:
Format:
Send restorals:
Retry time seconds:
Retry count:
Event notification:
Enter the secondary receiver’s phone number. This can contain up
to 20 digits (0-9, *, #, and ,). The comma causes a two-second delay
in dialing. The number or hash symbol (#) and the asterisk symbol
(*) are used with calling feature codes and services. Consult your
telephone service provider.
CID: Contact ID is the alarm format that the monitoring facility
(DACR) will receive. See “Default contact ID event codes” on page
39.
Set send restorals to:
Yes: Sends off-normal event restorals to the monitoring facility
(DACR). Required setting for UL/ULC installations. See “UL 864
programming requirements” on page 31 for details.
No: Does not send off-normal event restorals to the monitoring
facility (DACR)
Set retry time to 1 to 45 seconds. Specifies the wait time between
each time the dialer attempts a connection to the DACR.
Set the retry count to 5 to 10 attempts. Specifies how many times
the dialer will attempt to call the DACR before timing out.
Set event notification (event reporting) to:
Device: Only device information is reported or transmitted, no zone
information. Note: This setting uses device event notification
settings for reporting events. Make sure your device event
notification settings are correct. See “Central monitoring station
device programming” on page 108.
Zone: When a device is a member of a zone, only the zone
information is reported or transmitted. Device information is not
reported or transmitted. Note: This setting uses zone event
notification settings for reporting events. Make sure the zone event
notification settings are correct. See “Loop event programming” on
page 122.
Event: Only the event type (alarm, supervisory, trouble, etc.) is
reported or transmitted, no device or zone information. Note: This
setting uses the CMS event notification settings for reporting
events. Make sure the event notification settings are correct. See
“Central monitoring station device programming” on page 108.
Line 1 and 2
Dialing:
Cut duration/supervision:
Program line 1 options, and then program line 2 options. When you
have finished programming each line, choose Save.
Select Tone or Pulse dialing.
Set the cut duration/supervision to Off or 10 to 120 seconds.
Specifies the length of time a phone line trouble is detected before
reporting the trouble.
Tone wait seconds Set tone wait to Off or 1 to 30 seconds. Specifies how long the
dialer waits to get a dial tone.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals