Chapter 2: Front panel programming
118 Vigilant VS1 and VS2 Technical Reference Manual
Table 32: Panel operation options
Option Description
Language Select the desired display language: English or French
Marketplace Select the desired marketplace: U.S. or Canada
AC fail delay Set the AC fail delay time to:
Off: Off-premises notification of an AC power failure is immediate.
Note: The “off” setting is not acceptable for UL/ULC installations.
See “UL 864 programming requirements” on page 31 for details.
1 to 15 hours: Delays the off-premises notification of an AC power
failure by the time period selected
Zone resound Set zone resound to:
On: NACs resound each time a device in the zone goes into alarm
even if they were silenced
Off: Inhibits the NACs from turning on again (after they were
silenced) when a second device in the zone goes into alarm. Note:
The “off” setting is not acceptable for UL/ULC installations. See “UL
864 programming requirements” for details.
Reset inhibit Set the time to:
Off: Panel reset is operational immediately after NACs turn on
1 minute: Panel reset is operational one minute after NACs turn on
Auto signal silence Set auto signal silence to:
Off: Does not allow the panel to automatically silence the signals
5 to 30 minutes: Allows the panel to automatically silence the
signals after the selected time period expires
Suite signal silence Set the timer duration. The range of possible values is 1 to 10
minutes. The default value is 10 minutes.
Day start Set the start time for daytime sensitivity
Night start Set the start time for nighttime sensitivity
Date Set the date format to:
U.S.: MM/DD/YYYY
Canada: DD/MM/YYYY
LCD banner Enter the desired banner text for line one and line two using the
keypad. Each line is capable of up to 20 characters. When you have
finished, choose Save.
Aux power reset On: “Reset” temporarily turns off the resettable aux power output
Off: “Reset” does not turn off the resettable aux power output