Chapter 2: Front panel programming
124 Vigilant VS1 and VS2 Technical Reference Manual
To program loop events:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Loop Events.
4. Select the loop event.
5. Choose Event Notification.
6. Set the event notification. See the default settings in
the table above.
Printer: Yes or No. Specifies if event information is
printed
Dialer:
Acct 1 & 2: Event information is sent to both dialer
accounts
Acct 1: Event information is sent to dialer account
one
Acct 2: Event information is sent to dialer account
two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent
to the connected network
CID: Contact ID event code (000 to 999)
7. When finished, choose Save.
8. Repeat steps 6 to 9 for each loop event.
9. Press the Menu button to exit menu mode, or
continue programming.
Advanced Program
Panel Operation
Panel Events
Loop Events
Loop Events
Loop 1 Initializing
Loop 1 Fault
Loop 1 Map Fault
Loop 1 Initializing
Event Notification
Trouble
Printer Yes<>
Dialer Account 1&2
NET Yes<>
Trouble
NET Yes<>
CID 110

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals