Event ID Event description Event ID Event description
005 Loop 1 uncfgrd trouble: A device on
loop 1 that is not programmed went
into trouble
057 Net recvr config fault: The panel
failed to communicate with the
network receiver after a
configuration change
006 Loop 1 map mismatch: The loop 1
map in RAM and the loop 1 map in
the database do not match
058 NAC 1 trouble: An open or short has
been detected on NAC 1 or there is a
problem with the EOL
007 Loop 1 over limits: There are too
many devices on loop 1
059 NAC 2 trouble: An open or short has
been detected on NAC 2 or there is a
problem with the EOL
008 Loop 1 device 000: A device on loop
1 has an address set to zero
060 NAC 3 trouble: An open or short has
been detected on NAC 3 or there is a
problem with the EOL
009 Loop 1 mapping: Loop 1 is mapping
devices
061 NAC 4 trouble: An open or short has
been detected on NAC 4 or there is a
problem with the EOL
010 Loop 2 initialization: Loop 2 is
starting up
062 Printer trouble: The printer is either
offline, out of paper, or disconnected
011 Loop 2 fault: A short or open was
detected on loop 2 affecting the
communications between the panel
and the devices on the loop
063 Annunciator 1 trouble: An open or
short has been detected on
annunciator 1
012 Loop 2 map fault: A mapping fault
was detected on loop 2 while the
panel was mapping the devices
064 Annunciator 2 trouble: An open or
short has been detected on
annunciator 2
013 Loop 2 card fault: The loop 2 card is
not present or it is not working
properly
065 Annunciator 3 trouble: An open or
short has been detected on
annunciator 3
014 Loop 2 uncfgrd alarm: A device on
loop 2 that is not programmed went
into alarm
066 Annunciator 4 trouble: An open or
short has been detected on
annunciator 4
015 Loop 2 uncfgrd trouble: A device on
loop 2 that is not programmed went
into trouble
067 Annunciator 5 trouble: An open or
short has been detected on
annunciator 5
016 Loop 2 map mismatch: The loop 2
map in RAM and the loop 2 map in
the database do not match
068 Annunciator 6 trouble: An open or
short has been detected on
annunciator 6
017 Loop 2 over limits: There are too
many devices on loop 2
069 Annunciator 7 trouble: An open or
short has been detected on
annunciator 7
018 Loop 2 device 000: A device on loop
2 has an address set to zero
070 Annunciator 8 trouble: An open or
short has been detected on
annunciator 8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals