Appendix D: Applications
Vigilant VS1 and VS2 Technical Reference Manual 255
In-Suite Signal Silence Correlation
Input Output
Occupant and hallway inputs on all floors Occupant sounders on all floors
How this application works
This application silences the audible alarm signals inside dwelling units, except on the
floor of the alarm.
For example, if an alarm occurs on the third floor:
The Floor 3 Correlation turns on the sounders on the floor of the alarm (including
those inside dwelling units).
The Hallway Correlation turns on hallway sounders throughout the building.
The In-Suite Signal Silence Correlation turns on sounders in residences on all other
floors.
After 60 seconds, the In-Suite Signal Silence Correlation, which has in-suite signal
silence enabled, silences sounders inside dwelling units on all other floors. These
signals remain off until the in-suite signal silence timer expires or a subsequent
alarm comes in.