Appendix E: Device types to personality codes correlation
260 Vigilant VS1 and VS2 Technical Reference Manual
Model Device type Personality code
MAB Alarm (1) Alarm - NO latching (Class B)
MAB Alarm Class A (9) Alarm - NO latching (Class A)
MAB Continuous Non-Silenceable (16) Signal - supervised output (Class B)
MAB Continuous Non-Silenceable
(Latched)
(16) Signal - supervised output (Class B)
MAB Continuous Non-Silenceable
Class A
(15) Signal - supervised output (Class A)
MAB Continuous Non-Silenceable
Class A (Latched)
(15) Signal - supervised output (Class A)
MAB Continuous Silenceable (16) Signal - supervised output (Class B)
MAB Continuous Silenceable Class A (15) Signal - supervised output (Class A)
MAB Heat (1) Alarm - NO latching (Class B)
MAB Heat Class A (9) Alarm - NO latching (Class A)
MAB Monitor (3) Active - NO nonlatching (Class B)
MAB Monitor Class A (11) Active - NO nonlatching (Class A)
MAB None (0) No Personality
MAB Pull Station (1) Alarm - NO latching (Class B)
MAB Pull Station Class A (9) Alarm - NO latching (Class A)
MAB Remote AC Fail (3) Active - NO nonlatching (Class B)
MAB Remote AC Fail Class A (11) Active - NO nonlatching (Class A)
MAB Remote Drill (3) Active - NO nonlatching (Class B)
MAB Remote Reset (3) Active - NO nonlatching (Class B)
MAB Remote Signal Silence (3) Active - NO nonlatching (Class B)
MAB Smoke (1) Alarm - NO latching (Class B)
MAB Smoke Class A (9) Alarm - NO latching (Class A)
MAB Supervised Output (16) Signal - supervised output (Class B)
MAB Supervised Output (Latched) (16) Signal - supervised output (Class B)
MAB Supervised Output Class A (15) Signal - supervised output (Class A)
MAB Supervised Output Class A
(Latched)
(15) Signal - supervised output (Class A)
MAB Supervisory Latching (4) Active - NO latching (Class B)
MAB Supervisory Latching Class A (12) Active - NO latching (Class A)
MAB Supervisory Nonlatching (3) Active - NO nonlatching (Class B)
MAB Supervisory Nonlatching Class A (11) Active - NO nonlatching (Class A)
MAB Water Flow (2) Alarm - NO delayed latching (Class B)