Appendix E: Device types to personality codes correlation 
262  Vigilant VS1 and VS2 Technical Reference Manual 
Model  Device type  Personality code 
MCT2  Smoke  (1) Alarm - NO latching (Class B) 
MCT2  Supervisory Latching  (4) Active - NO latching (Class B) 
MCT2  Supervisory Nonlatching  (3) Active - NO nonlatching (Class B) 
MCT2  Unlatch Outputs  (3) Active - NO nonlatching (Class B) 
MCT2  Water Flow  (2) Alarm - NO delayed latching (Class B) 
MIO  Relay Non-Silence NC  (32) Monitor - NO input/output NC 
MIO  Relay Non-Silence NC (Latched)  (32) Monitor - NO input/output NC 
MIO  Relay Non-Silence NO  (31) Monitor - NO input/output NO 
MIO  Relay Non-Silence NO (Latched)  (31) Monitor - NO input/output NO 
MIO  Relay Silence NC  (32) Monitor - NO input/output NC 
MIO  Relay Silence NO  (32) Monitor - NO input/output NC 
MM1  Monitor  (3) Active - NO nonlatching (Class B) 
MM1  Unlatch Outputs  (3) Active - NO nonlatching (Class B) 
MRM1  Monitor  (23) Riser monitor - 24 VDC 
PHS  Smoke Heat  (1) Alarm - NO latching (Class B) 
PHS  Smoke Verified  (1) Alarm - NO latching (Class B) 
PHS  Supervisory Latching  (1) Alarm - NO latching (Class B) 
PHS  Supervisory Nonlatching  (3) Active - NO nonlatching (Class B) 
PS  Smoke  (1) Alarm - NO latching (Class B) 
PS  Smoke Verified  (1) Alarm - NO latching (Class B) 
PS  Supervisory Latching  (1) Alarm - NO latching (Class B) 
PS  Supervisory Nonlatching  (3) Active - NO nonlatching (Class B) 
RM1  Monitor  (23) Riser monitor - 24 VDC 
SD  Duct Alarm  (1) Alarm - NO latching (Class B) 
SD  Duct Supervisory Latching  (4) Active - NO latching (Class B) 
SD  Duct Supervisory Nonlatching  (3) Active - NO nonlatching (Class B) 
UM  2Wire Alarm  (13) Alarm - two-wire smoke unverified (Class B) 
UM  2Wire Alarm Class A  (20) Alarm - two-wire smoke unverified (Class A) 
UM  2Wire Alarm Verify  (14) Alarm - two-wire smoke verified (Class B) 
UM  2Wire Alarm Verify Class A  (21) Alarm - two-wire smoke verified (Class A) 
UM  Alarm  (1) Alarm - NO latching (Class B) 
UM  Alarm Class A  (9) Alarm - NO latching (Class A) 
UM  Continuous Non-Silenceable  (16) Signal - supervised output (Class B)