REMOTE CONTROL
81
Query Syntax
:SYSTem:COMMunicate:USB:FRONt:STATe?
Return parameter
+0
<NR1>Absent
+1
<NR1>Mass Storage
:SYSTem:COMMunicate:USB:REAR:MODE
Set
Query
Description
Sets or queries the speed of the rear panel USB B
port. This setting is applied only after the unit is
reset.
Syntax
:SYSTem:COMMunicate:USB:REAR:MODE
{<NR1>|AUTO|FULL}
Query Syntax
:SYSTem:COMMunicate:USB:REAR:MODE?
Parameter
0 | AUTO
AUTO
1 | FULL
FULL
Return parameter
<NR1>
+0
AUTO
+1
FULL
:SYSTem:COMMunicate:USB:REAR:STATe
Query
Description
Queries the rear panel USB-B port state.
Query Syntax
:SYSTem:COMMunicate:USB:REAR:STATe?
Return parameter
+0
<NR1>Absent
+1
<NR1>Connected to the PC
:SYSTem:CONFigure:RAMP[:MODE]
Set
Query
Description
Sets or queries the ramp mode for the power
supply or disables the ramp mode.
Syntax
:SYSTem:CONFigure:RAMP[:MODE]
{<NR1>|DISable|TIME|VOLTage}
Query Syntax
:SYSTem:CONFigure:RAMP[:MODE]?
Parameter
0 | DISable
Disables ramp mode.
1 | TIME
Time mode
2 | VOLTage
Voltage mode

Table of Contents

Other manuals for GW Instek APS-7000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GW Instek APS-7000 Series and is the answer not in the manual?

GW Instek APS-7000 Series Specifications

General IconGeneral
BrandGW Instek
ModelAPS-7000 Series
CategoryAC Power Distribution
LanguageEnglish

Related product manuals