38 UDC3300 Limit Controller Product Manual 1/01
4.4 Input 1 Parameters Set Up Group, Continued
Input 1 group
prompts, continued
Table 4-3 Input 1 Group Definitions, Continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
XMITTER
(not available for FM
models)
B TC
E TC H
E TC L
J TC H
J TC L
K TC H
K TC L
NNM H
NNM L
NM90 H
NM90 L
NIC TC
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
LINEAR
SQROOT
TRANSMITTER CHARACTERIZATIONThis selection
lets you instruct the controller to characterize a linear input
to represent a non-linear one.
NOTE: Prompt only appears when a linear actuation is
selected at prompt IN1 TYPE.
FOR EXAMPLE: If input 1 is a 4 to 20 mA signal, but the
signal represents a type "K" thermocouple; select "K TC
H" and the controller will characterize the 4 to 20 mA
signal so that it is treated as a type "K" thermocouple input
(high range).
B Type Thermocouple
E Type Thermocouple High
E Type Thermocouple Low
J Type Thermocouple High
J Type Thermocouple Low
K Type Thermocouple High
K Type Thermocouple Low
NNM NiNiMo Type Thermocouple High
NNM NiNiMo Type Thermocouple Low
NiMo-NiCo Type Thermocouple High
NiMo-NiCo Type Thermocouple Low
NIC Nicrosil Nisil Thermocouple
R Type Thermocouple
S Type Thermocouple
T Type Thermocouple High
T Type Thermocouple Low
W5W26 Type Thermocouple High
W5W26 Type Thermocouple Low
100 OhmRTD
100 Ohm RTD low
200 OhmRTD
500 OhmRTD
Radiamatic (Type RH)
Radiamatic (Type RI)
Linear Range
Extracts Square Root
Continued on next page