Installing a 8 SFF drive cage optionInstalling a 8 SFF drive cage option
Installing the E3.S drive cageInstalling the E3.S drive cage
Installing the 2 SFF stacked drive cageInstalling the 2 SFF stacked drive cage
Installing a 8 SFF drive cage optionInstalling a 8 SFF drive cage option
PrerequisitesPrerequisites
Before you perform this procedure, make sure that you have the following items available:
T-10 Torx screwdriver
T-15 Torx screwdriver
About this taskAbout this task
This server supports several 8 SFF drive cage options with different backplanes. This drive cage supports SAS, SATA, and U.3 PCIe4 NVMe
drives.
CAUTION:CAUTION:
A discharge of static electricity from a finger or other conductor might damage system boards or other static-sensitive
devices. To prevent damage, observe antistatic precautions.
CAUTION:CAUTION: To prevent improper cooling and thermal damage, do not operate the server unless all bays are populated with
either a component or a blank.
ProcedureProcedure
1. If installed, remove the front bezel .
2. Power down the server.
3. If installed, open the cable management arm .
4. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
5. Disconnect all peripheral cables from the server.
6. Remove the server from the rack .
7. Place the server on a flat, level work surface.
8. Remove the access panel .
9. Do one of the following:
Remove the air baffle .
Remove the processor mezzanine tray .
10. Remove the fan cage.
11. Remove the drive box blank:
a. Remove the drive box blank screws (callout 1).