Removing and replacing the Removing and replacing the rackrack rails rails
PrerequisitesPrerequisites
If you are replacing the rack mounting rails from a threaded-hole rack, make sure that you have a Phillips No. 2 screwdriver available.
ProcedureProcedure
1. Power down the server.
2. Remove the cable management arm .
3. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4. Disconnect all peripheral cables from the server.
5. Remove the server from the rack.
6. Place the server on a flat, level surface.
7. Slide and hold the white release tab in the direction shown (callout 1), and slide out the server tray from the rack (callout 2).
8. If you are replacing a rack mounting rail, do the following:
a. If installed, remove the shipping screw from the rear rack column.