EasyManua.ls Logo

IAI RoboNet - Page 67

IAI RoboNet
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
Part 1 S
p
ecification
Relative address from beginning
Command name
CC-Link DeviceNet
PROFIBUS
RS485SIO *1
PLC output (request) PLC input (response)
RY 2*/RX 2* +2 +4/+5 1006H
RY 3*/RX 3* +3 +6/+7 Position number
RY 4*/RX 4* +4 +8/+9 Deceleration data *6
RY 5*/RX 5* +5 +10/+11 0
RY 6*/RX 6* +6 +12/+13 Axis number 0 to FH
Write deceleration
RY 7*/RX 7* +7 +14/+15 Cannot be used.
RY 2*/RX 2* +2 +4/+5 1007H
RY 3*/RX 3* +3 +6/+7 Position number
RY 4*/RX 4* +4 +8/+9 0000 to 00FFH
(00FFH, maximum current)
RY 5*/RX 5* +5 +10/+11 0
RY 6*/RX 6* +6 +12/+13 Axis number 0 to FH
Write push-current
limiting value *7
RY 7*/RX 7* +7 +14/+15 Cannot be used.
RY 2*/RX 2* +2 +4/+5 1008H
RY 3*/RX 3* +3 +6/+7 Position number
RY 4*/RX 4* +4 +8/+9 0000 to 00FFH
(00FFH, maximum current)
RY 5*/RX 5* +5 +10/+11 0
RY 6*/RX 6* +6 +12/+13 Axis number 0 to FH
Write load current
threshold
RY 7*/RX 7* +7 +14/+15 Cannot be used.
If the command has been
successful, the same value
set in the request is
returned as a response.
For error responses, refer
to (4), “Error Responses.”
*1 In byte address specification, the smaller byte address on the left corresponds to the upper byte of 1-word data, while the
larger byte address on the right corresponds to the lower byte of 1-word data.
*2 Set as a hexadecimal number using a 32-bit signed integer (unit: 0.01 mm).
Example) To set +25.4 mm, specify “0009ECH” (decimal number: 2540).
The maximum settable value is +9999.99 mm = 999999 (decimal number) = 0F423FH (hexadecimal number).
Since a negative value is indicated as a 2’s complement, the most significant bit becomes “1.”
Set position data within the soft stroke range.
*3 Axis numbers (0) to (15) correspond to data 00 to 0FH.
*4 Set as a hexadecimal number using a 32-bit signed integer (unit: 0.01 mm).
Example) To set +25.4 mm, specify “000009ECH” (decimal number: 2540).
Set within the soft stroke range.
*5 Set as a hexadecimal number using a 32-bit integer (unit: 0.01 mm/sec).
Example) To set 200 mm/sec, specify “000000C8H” (decimal number: 200).
*6 Set as a hexadecimal number using a 16-bit integer (unit: 0.01 G).
Example) To set 0.2 G, specify “0014H” (decimal number: 20).
The maximum settable value is 2G, specifying “00C8H” (decimal number: 200)
*7 If push-current limiting value is not set in the position table before the write command is executed, the data will not be
rewritten.
*8 The asterisk (*) in CC-Link addresses is a value between 0 and F.

Table of Contents

Related product manuals