Table 35: PTX10001-36MR System Alarm Messages
(Connued)
Component Alarm Type CLI Message Recommended Acon
PEM
pem-number
is not powered
Check the power cord connecon
and reconnect, if necessary.
PEM
pem-number
is not supported
Replace the power supply with a
supported power supply.
PEM
pem-number
Not OK
Indicates a problem with the
incoming AC power or outgoing DC
power. Report the error to customer
support.
Minor (yellow)
PEM
pem-number
Absent
A power supply is not installed.
Install a supported power supply in
the appropriate slot.
PEM
pem-number
Power Supply Type
Mismatch
Check if there is a mix of AC and
DC power supplies in the same
chassis. Reboot the device with only
AC or only DC power supplies.
PEM
pem-number
Removed
Replace the removed power supply.
Temperature
sensors
Major (red)
sensor-location
Temp Sensor Fail
Check the system log for the
following message and report it to
customer support:
Temp sensor
sensor-number
failed,
where
sensor-number
ranges from
1 through 10.
131