Table 9: PTX10001-36MR Fan Modules
Fan Module Label on the Fan
Module
Direcon of Airow in the Fan
Module
Power Supplies
JNP-FAN2-1RU AIR OUT Front-to-back, that is, air comes in
through vents on the end with the
network ports; air exhausts out the
end with the fans.
You must install only
power supplies that have
AIR OUT labels in devices
in which the fan modules
have AIR OUT labels.
Airow Through the Chassis
In the PTX10001-36MR cooling system, cool air enters through the vents in the port panel and hot air
exhausts through the FRU panel. This type of airow is known as
airow out
or
port-to-FRU
airow.
When the chassis is installed, it must be posioned so that the FRUs are next to the
hot aisle
. Figure 11
on page 23 shows the airow through the chassis.
Figure 11: Airow Through the PTX10001-36MR Chassis (Port-to-FRU)
23