Table 33: Alarms for Services Gateway Chassis Components
Alarm SeverityActionAlarm ConditionsComponent
Steady red (major)
•
Check and adjust the room
temperature, if possible.
•
Check the air flow and ensure
that the airflow through the
services gateway is
unobstructed.
•
Replace the failed fan module
to avoid failure of the other fan
modules.
•
Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822
(toll-free within the United
States and Canada) or
1-408-745-9500 (from outside
the United States).
At least one of the fans
have failed.
Fan
Yellow (minor)/Red
(major)
•
Check the room temperature.
•
Check the air flow.
•
Run all the Fans at full speed.
•
Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822
(toll-free within the United
States and Canada) or
1-408-745-9500 (from outside
the United States).
The services gateway
chassis temperature is too
warm.
Red (major)Install the missing fan module.Missing fan module
Yellow (minor)
•
Check if the fan is spinning
more than the configured
speed.
•
Replace the fan module as it is
likely to fail.
Fan over-speeding
Yellow (minor)Fan spinning below its
speed
128