Table 33: Alarms for Services Gateway Chassis Components
Alarm SeverityActionAlarm ConditionsComponent
Steady red (major)
Check and adjust the room
temperature, if possible.
Check the air flow and ensure
that the airflow through the
services gateway is
unobstructed.
Replace the failed fan module
to avoid failure of the other fan
modules.
Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822
(toll-free within the United
States and Canada) or
1-408-745-9500 (from outside
the United States).
At least one of the fans
have failed.
Fan
Yellow (minor)/Red
(major)
Check the room temperature.
Check the air flow.
Run all the Fans at full speed.
Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822
(toll-free within the United
States and Canada) or
1-408-745-9500 (from outside
the United States).
The services gateway
chassis temperature is too
warm.
Red (major)Install the missing fan module.Missing fan module
Yellow (minor)
Check if the fan is spinning
more than the configured
speed.
Replace the fan module as it is
likely to fail.
Fan over-speeding
Yellow (minor)Fan spinning below its
speed
128