Table 20: Clearance Requirements for the SRX4600 Services Gateway
Requirement for Clearance
Recommended
ClearanceLocation
Space for service personnel to remove and
install hardware components
24.00 in. (60.90 cm)Front of the chassis
Space for service personnel to remove and
install hardware components
24.00 in. (60.90 cm)Rear of the chassis
Space for cable management and organization2.50 in. (6.35 cm)Between front-mounting flange and
rack or cabinet edge
Space for the cooling system to function
properly and to maintain unrestricted airflow
around the chassis
6.00 in. (15.24 cm)Between both sides of the chassis and
any non-heat-producing surface such
as a wall or cabinet side
RELATED DOCUMENTATION
Understanding the SRX4600 Services Gateway Chassis | 23
SRX4600 Rack and Cabinet Requirements
IN THIS SECTION
SRX4600 Services Gateway Rack Requirements | 50
Cabinet Requirements | 51
SRX4600 Services Gateway Rack Requirements
You can mount the device on four-post racks.
Rack requirements consist of: