Replacing an SRX4600 Services Gateway DC Power Supply
IN THIS SECTION
Removing the SRX4600 Services Gateway DC Power Supply | 95
Installing the SRX4600 Services Gateway DC Power Supply | 97
Each power supply is a field-replaceable unit (FRU) installed in the rear panel of the SRX4600 Services
Gateway. You can remove and replace a power supply without powering off the services gateway or
disrupting services gateway functions.
NOTE: All the power supplies must be installed and operational for optimal functioning of the
services gateway.
Removing the SRX4600 Services Gateway DC Power Supply
You can remove a DC power supply without powering off the services gateway or disrupting services
gateway functions.
Ensure that you have the following tools and parts available:
•
Electrostatic discharge (ESD) grounding strap
•
An antistatic bag or an antistatic mat
•
Socket nut driver
•
A cover panel for the power supply slot
NOTE: Before you remove a power supply from the services gateway, ensure that you have
taken the necessary precautions to prevent ESD damage (see Prevention of Electrostatic Discharge
Damage).