Rack type
•
Mounting bracket hole spacing
•
Rack size and strength
•
Rack connection to the building structure
Table 21 on page 51 provides the rack requirements and specifications.
Table 21: Rack Requirements and Specifications
GuidelinesRack Requirement
You can mount the device on a rack that provides bracket holes or hole patterns
spaced at 1 U (1.75 in. or 4.45 cm) increments and meets the size and strength
requirements to support the weight.
A U is the standard rack unit defined by the Electronics Industry Association.
Rack type
The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so
that the device can be mounted in any rack that provides holes spaced at that
distance.
Mounting bracket hole spacing
•
Ensure that the rack complies with the size and strength standards of a 19-in.
rack as defined by the Electronics Industry Association.
•
Ensure that the rack rails are spaced widely enough to accommodate the
external dimensions of the device chassis. The outer edges of the front-mounting
brackets extend the width of the chassis to 19 in. (48.2 cm).
•
The rack must be strong enough to support the weight of the device.
•
Ensure that the spacing of rails and adjacent racks provides for proper clearance
around the device and rack.
Rack size and strength
•
Secure the rack to the building structure.
•
If earthquakes are a possibility in your geographical area, secure the rack to the
floor.
•
Secure the rack to the ceiling brackets as well as wall or floor brackets for
maximum stability.
Rack connection to building
structure
Cabinet Requirements
You can mount the device in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
•
Cabinet size
51