Rack type
Mounting bracket hole spacing
Rack size and strength
Rack connection to the building structure
Table 21 on page 51 provides the rack requirements and specifications.
Table 21: Rack Requirements and Specifications
GuidelinesRack Requirement
You can mount the device on a rack that provides bracket holes or hole patterns
spaced at 1 U (1.75 in. or 4.45 cm) increments and meets the size and strength
requirements to support the weight.
A U is the standard rack unit defined by the Electronics Industry Association.
Rack type
The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so
that the device can be mounted in any rack that provides holes spaced at that
distance.
Mounting bracket hole spacing
Ensure that the rack complies with the size and strength standards of a 19-in.
rack as defined by the Electronics Industry Association.
Ensure that the rack rails are spaced widely enough to accommodate the
external dimensions of the device chassis. The outer edges of the front-mounting
brackets extend the width of the chassis to 19 in. (48.2 cm).
The rack must be strong enough to support the weight of the device.
Ensure that the spacing of rails and adjacent racks provides for proper clearance
around the device and rack.
Rack size and strength
Secure the rack to the building structure.
If earthquakes are a possibility in your geographical area, secure the rack to the
floor.
Secure the rack to the ceiling brackets as well as wall or floor brackets for
maximum stability.
Rack connection to building
structure
Cabinet Requirements
You can mount the device in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
Cabinet size
51