105
4
Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
SECTION 4 MODBUS PROTOCOL
4.5.2 KLEA Setting Parameters
Operator/programmer should use‘10H - Write Multiple Registers and‘06H - Write Single
Register to change settings parameters.
Operator/programmer should use ‘0x3H - Read Holding Registers function to read setting
parameters.
1 register -> comprises of 2 bytes.
After Klea setting parameters have been changed, in order for the new values to be
saved in non-volatile memory;
0x0000 should be written to register 1998, and
0x0001 should be written in register 1999, within 60 seconds following the last setting change.
Only after that, changes will be stored in the permanent memory.
NOTE1:
3 parameters given with“RO (Read Only)” in Table 4-5 are read-only data. They cannot be
changed by the user. This data is as given below:
Serial Number
Firmware Version
Compiler Version
NOTE2:
1998 addressed variable at the end of Table 4-5 is a W (only writable)” variable.
Tablo 4-5 Setting Parameters
Address Parameter Data Type Descript. R/W Unit Low Limit High Limit
Network Settings
2000 Current Transf. Ratio (CTR) 32 bit flo t - R/W - 1 5000
2002 Voltage Transf. Ratio (VTR) 32 bit flo t - R/W - 1 5000
2004 Connection 32 bit flo t SL1 R/W - 0 2
2006 Demand Period 32 bit flo t - R/W dakika 1 60
2008 Power Unit 32 bit flo t SL2 R/W - 0 1
Energy Settings
2010 T1_1 Start Time 32 bit int. - R/W hour 0 23
2012 T1_2 Start Time 32 bit int. - R/W hour 0 23
2014 T1_3 Start Time 32 bit int. - R/W hour 0 23