Safety instructions
Safety instructions for the installation according to UL
2
114
EDK82EV903 DE/EN/FR 5.1
2.5 Safety instructions for the installation according to UL
Warnings!
ƒ Motor Overload Protection
For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
ƒ Branch Circuit Protection
The integral solid state protection does not provide branch circuit
protection.
Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
ƒ Please observe the specifications for fuses and screw−tightening torques in
these instructions.
ƒ E82xV153K4B ... E82xV303K4B:
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses
Maximum surrounding air temperature: 0 ... +50 °C
> +40 °C: reduce the rated output current by 2.5 %/°C
Use 60/75 °C or 75 °C copper wire only.
ƒ E82xV453K4B ... E82xV903K4B:
Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses
Maximum surrounding air temperature: 0 ... +50 °C
> +40 °C: reduce the rated output current by 2.5 %/°C
Use 60/75 °C or 75 °C copper wire only.

Table of Contents

Other manuals for Lenze 8200 vector series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8200 vector series and is the answer not in the manual?

Lenze 8200 vector series Specifications

General IconGeneral
CategoryDC Drives
Overload capacity150% for 60 seconds
Protection classIP20
Mains voltage380V to 480V AC
Control methodVector control
Communication optionsCANopen
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Humidity≤ 95% relative humidity, non-condensing
Series8200 vector

Related product manuals