Electrical installation
Wiring
Mains choke/mains filter assignment
5
140
EDK82EV903 DE/EN/FR 5.1
5.2 Wiring
5.2.1 Mains choke/mains filter assignment
Operation at rated power on 400/500 V mains, 3/PE
8200 vector Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component Component
Type Var. Type C2 Max. [m] C1 Max. [m]
E82xV153K4B 2xx ELN3−0088H035−001
EZN3A0110H030 25 EZN3B0110H030
2)
EZN3B0110H030U
3)
50
E82ZN22334B230 50
10
5)
E82ZN22334B230 10
0
5)
E82ZZ15334B230 50
10
5)
E82ZZ15334B230 10
0
5)
3xx − − 50 − 10
E82xV223K4B 2xx ELN3−0075H045
EZN3A0080H042 25 EZN3B0080H042 50
E82ZN22334B230 50
10
5)
E82ZN22334B230 10
0
5)
3xx − − 50 − 10
E82xV303K4B 2xx ELN3−0055H055
EZN3A0055H060 25 EZN3B0055H060 50
E82ZN30334B230 50
10
5)
E82ZN30334B230 10
0
5)
3xx − − 50 10
E82xV453K4B 2xx ELN3−0038H085
EZN3A0037H090 25 EZN3B0037H090 50
E82ZN45334B230 50
10
5)
E82ZN45334B230 10
0
5)
3xx − − 50 10
E82xV553K4B 2xx ELN3−0027H105
EZN3A0030H110
EZN3A0030H110N001
4)
25 EZN3B0030H110 50
E82ZN55334B230 50
10
5)
E82ZN55334B230 10
0
5)
3xx − − 50 − 10
E82xV753K4B 2xx ELN3−0022H130
EZN3A0022H150 25 EZN3B0022H150 50
E82ZN75334B230 50
10
5)
E82ZN75334B230 10
0
5)
3xx − − 50 − 10
E82xV903K4B 2xx ELN3−0017H170
EZN3A0017H200 25 EZN3B0017H200 50
E82ZN90334B230 50
10
5)
E82ZN90334B230 10
0
5)
3xx − − 50 − 10
2)
Side−mounted filter
3)
Footprint filter
4)
For E82DV553K4B (push−through technique)
5)
at switching frequency f
ch
= 16 kHz; the interference voltage category C1 cannot be achieved
Operation with increased rated power
System Manual