Function library
Function blocks
9.2.27 Digital frequency ramp function generator (DFRFG)
9-106
L
EDSVS9332S-D11 EN 3.0
9.2.27.2 Quick stop
Removes the drive from the network and brakes it to standstill.
z Activate with DFRFG-QSP = HIGH.
z Set deceleration time via C0753.
z Store the setpoint phase detected at DFRFG-IN.
z Approach the setpoint phase via the profile generator after resetting the quick stop request.
t
DFRFG-IN
C075
C0751 C0751
DFRFG-QSP
t
DFRFG-OUT
C0753
Fig. 9-68 Quick stop DFRFG
9.2.27.3 Ramp function generator stop
Maintains the state of the profile generator during operation.
z Activate with DFRFG-STOP = HIGH.
z Output of the last state at DFRFG-OUT.
z Store the setpoint phase detected at DFRFG-IN.
z Approach the setpoint phase via the profile generator after resetting the stop request.
t
DFRFG-IN
C075
DFRFG-STOP
t
DFRFG-OUT
Fig. 9-69 Ramp function generator stop